CENELEC

Project
| Reference | EN 60332-1-2:2004 |
|---|---|
| Title | Tests on electric and optical fibre cables under fire conditions - Part 1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame |
| Project Number | 15821 |
| Abstract/Scope | Specifies the procedure for testing the resistance to vertical flame propagation for a single vertical electrical insulated conductor or cable, or optical fibre cable, under fire conditions. The apparatus is given in EN 60332-1-1. NOTE 1 Testing to EN 60332-1-2 may be performed simultaneously with that to EN 60332-1-3 if required. Recommended requirements for performance are given in Annex A. EN 60332-1-2 specifies the use of a 1 kW pre-mixed flame and is for general use, except that the procedure specified may not be suitable for the testing of small single insulated conductors or cables of less than 0,5 mm² total cross-section because the conductor melts before the test is completed, or for the testing of small optical fibre cables because the cable is broken before the test is completed. In these cases, the procedure given in EN 60332-2-2 is recommended. NOTE 2 Since the use of insulated conductor or cable which retards flame propagation and complies with the recommended requirements of this standard is not sufficient by itself to prevent propagation of fire under all conditions of installation, it is recommended that wherever the risk of propagation is high, for example in long vertical runs of bunches of cables, special installation precautions should also be taken. It cannot be assumed that because the sample of cable complies with the performance requirements recommended in this standard, that a bunch of cables will behave in a similar manner. (See EN 60332-3 series.) Has the status of a group safety publication in accordance with IEC Guide 104. |
| Status |
Published
|
Status
| Current Stage code | 6060 |
|---|---|
| Current Stage code date | 2004-11-15 |
| Current Stage code deadline | 2005-06-01 |
| Deadline date for vote |
Legal
| Directive(s) | LVD (2006/95/EC) |
|---|---|
| Mandate(s) | |
| Order Voucher |
Details
| IEC Technical Body | IEC/TC 20 |
|---|---|
| Reference Document | IEC 60332-1-2:2004 (EQV) |
| ICS | 13.220.40 - Ignitability and burning behaviour of materials and products 29.020 - Electrical engineering in general 29.060.20 - Cables |
| Keywords | Optical fibre; Fire conditions; Flame propagation; Insulated wire; Pre-mixed flame |
| Note | Supersedes EN 50265-2-1:1998 |
| A-Deviation(s) | |
| Special National Condition(s) |
Environment
|
Clause
|
Categories - Aspects
|
Product Life Cycle
|
Information
|
|---|
History
Implementation Dates
| date of Ratification (DOR) (1) | 2004-09-01 |
|---|---|
| date of Availability (DAV) (2) | 2004-11-15 |
| date of Announcement (DOA) (3) | 2004-12-01 |
| date of Publication (DOP) (4) | 2005-06-01 |
| date of Withdrawal (DOW) (5) | 2007-09-01 |
Relations
| Supersedes | EN 50265-2-1:1998 |
|---|---|
| Superseded by | |
| Normative reference (6) | IEC Guide 104:1997 EN 60332-1-1:2004 EN 60695-4:1995 |
(1) Date of ratification (dor) date when the Technical Board notes the approval of an EN (and HD for CENELEC), from which time the standard may be said to be approved
(2) Date of availability (dav) date when the definitive text in the official language versions of an approved CEN/CENELEC publication is distributed by the Central Secretariat
(3) Date of announcement (doa) latest date by which the existence of an EN (and HD for CENELEC), a TS or a CWA has to be announced at national level
(4) Date of publication (dop) latest date by which an EN has to be implemented at national level by publication of an identical national standard or by endorsement
(5) Date of withdrawal (dow) latest date by which national standards conflicting with an EN (and HD for CENELEC) have to be withdrawn
(6) This list of normative references is purely indicative. The only official list of normative reference is the list of the published standard.