CENELEC

Project
| Reference | EN 50525-3-31:2011 |
|---|---|
| Title | Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-31: Cables with special fire performance - Single core non-sheathed cables with halogen-free thermoplastic insulation, and low emission of smoke |
| Project Number | 21982 |
| Abstract/Scope | EN 50525-3-31 applies to non-sheathed single core cables insulated with halogen-free thermoplastic compound and having low emission of smoke and corrosive gases when exposed to fire. NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for absence of halogens (see Annex B of EN 50525-1). The cables are of rated voltages U0/U up to and including 450/750 V. NOTE 2 Cables rated 450/750 V may be used at 600/1 000 V when this cable is used in fixed installations with mechanical protection, within switchgear and control gear - see HD 516. For cables rated at 450/750 V there are two types, Type 1 and Type 2. Type 2 cables are required to meet a more severe test for resistance to flame propagation (EN 60332-3-24) than Type 1, and have particular suitability for installation in bunches (see also HD 516). The cables are intended for fixed wiring applications. The maximum conductor operating temperature for each of the cables in this standard is 70 °C. NOTE 3 HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-3-31 should be read in conjunction with EN 50525-1, which specifies general requirements. |
| Status |
Published
|
Status
| Current Stage code | 6060 |
|---|---|
| Current Stage code date | 2011-05-06 |
| Current Stage code deadline | 2012-01-17 |
| Deadline date for vote | 2010-10-08 |
Legal
| Directive(s) | LVD (2006/95/EC) |
|---|---|
| Mandate(s) | |
| Order Voucher |
Details
| IEC Technical Body | |
|---|---|
| Reference Document | |
| ICS | 29.060.20 - Cables |
| Keywords | Cable; Low voltage; Fire; Halogen-free; Thermoplastic insulation |
| Note | Supersedes HD 21.15 S1:2006 |
| A-Deviation(s) | |
| Special National Condition(s) |
Environment
|
Clause
|
Categories - Aspects
|
Product Life Cycle
|
Information
|
|---|
History
|
Stage
|
Date
|
Deadline Date
|
Documents
|
|---|---|---|---|
| 6060 | 2011-05-06 | 2012-01-17 | |
| 5099 | 2011-01-17 | 2011-02-14 | |
| 5060 | 2010-12-13 | 2011-01-17 | |
| 5020 | 2010-10-08 | 2010-12-10 | |
| 4099 | 2009-06-05 | 2010-08-12 | |
| 4060 | 2009-03-31 | 2009-06-18 | |
| 4020 | 2008-10-31 | 2009-03-27 | |
| 3099 | 2008-10-01 | 2008-11-01 | |
| 1099 | 2008-10-01 | 2009-04-01 | |
| 1000 | 2008-06-12 | 2008-09-30 |
Implementation Dates
| date of Ratification (DOR) (1) | 2011-01-17 |
|---|---|
| date of Availability (DAV) (2) | 2011-05-06 |
| date of Announcement (DOA) (3) | 2011-07-17 |
| date of Publication (DOP) (4) | 2012-01-17 |
| date of Withdrawal (DOW) (5) | 2014-01-17 |
Relations
| Supersedes | HD 21.15 S1:2006 |
|---|---|
| Superseded by | |
| Normative reference (6) |
(1) Date of ratification (dor) date when the Technical Board notes the approval of an EN (and HD for CENELEC), from which time the standard may be said to be approved
(2) Date of availability (dav) date when the definitive text in the official language versions of an approved CEN/CENELEC publication is distributed by the Central Secretariat
(3) Date of announcement (doa) latest date by which the existence of an EN (and HD for CENELEC), a TS or a CWA has to be announced at national level
(4) Date of publication (dop) latest date by which an EN has to be implemented at national level by publication of an identical national standard or by endorsement
(5) Date of withdrawal (dow) latest date by which national standards conflicting with an EN (and HD for CENELEC) have to be withdrawn
(6) This list of normative references is purely indicative. The only official list of normative reference is the list of the published standard.